It's not the same issue. The vast majority of kitchens in the US have 20 amp circuits (so 2,400 watts peak, 1,920 watts continuous) exclusively. It's a bog standard receptacle (NEMA 5-20R instead of 5-15R) that's backwards compatible with 15 amp plugs. In fact these days most 5-15R receptacles have identical guts to their 20 amp counterparts save for the additional provision for a horizontal blade.
The electrical code (NEC) has started moving towards requiring 20 amp circuits in other rooms and more 20 amp circuits in kitchens.
But they're staying shy of the amp limit on purpose. So designing for 20 amps would be somewhat of a boost but not enough. While doubling voltage would actually fix the problem.