With a higher voltage you can reduce your copper needs by a substantial amount. Seems if copper cost was a concern this would be what these data centers would do.


Replies

sidewndr46today at 3:40 PM

Agreed. I was kind of surprised to see 54 VDC mentioned. I am assuming this is low enough to meet some threshold for some kind of safety regulation. In other words, it doesn't shock you just 220 VAC would. I'm not entirely convinced of that however as it turns out bus bars are really dangerous in general. A 54 VDC bus bar won't shock you, but if you drop even a paperclip between the bus bar and a metal part that is grounded it basically disappears instantly in a small blast of plasma. The injury from that can be far worse than any shock you'd receive.