> Sure, but there are more appliances plugged in today than there were. The simplest evidence for this is that there are never enough outlets in an old (unrenovated) home.

Perhaps, but none of them are continuous load, which absolutely matters.

Rice cookers, microwave, stand mixers, air fryers, pressure cookers, etc are all short duration usage, not continuous load. If homeowners decide not to add dedicated kitchen circuits and instead use a 120V 12A load on a 120V 15A shared circuit and trip the overcurrent protection, that’s their own fault.

These loads don’t really matter in the way a heat pump, air conditioner, furnace fan, or water heater does, it’s a bunch of random kitchen appliances that you won’t be using simultaneously. Your utility does not even take the full non-continuous load into account when calculating the kVA demand of your electrical service. IIRC a random convenience duplex receptacle for non-continuous loads only adds like 180 VA (this is 1.5A at 120V with a power factor of 1) to the demand calculation.

You are correct in a technical sense that people have more devices they plug into a wall, but most of the power consumed by a home is to devices that are hardwired in, aka continuous loads, not cord and plug connected appliances.

The continuous load of a home should be lower than ever without electrifying heat. Every continuous load (which are almost exclusively motors and lighting) in a home is more efficient now than in the past due to variable frequency drives and electrically commutated motors.


Replies

queserayesterday at 11:43 PM

... but unless I'm mistaken, (something closer to) instantaneous load is the important factor for aluminum wire thermals.

Varying high loads are more significant than a continuous medium load in terms of the effects on wiring junctions.