Can someone ask: "what is the current carrying capacity of 25mm multicore armoured thermoplastic insulated cables with aluminium conductors, on perforated cable tray?" just to see how well it can look up information in BS 7671?


Replies

jaggederestyesterday at 10:52 PM

> what is the current carrying capacity of 25mm multicore armoured thermoplastic insulated cables with aluminium conductors, on perforated cable tray?

  This is an electrical engineering question rather than a software engineering one, but let me look it up for you.

  WEB SEARCH ("current carrying capacity 25mm multicore armoured thermoplastic insulated cable aluminium conductors perforated cable tray BS 7671")
   ↳ Found 10 results.

   Based on BS 7671 Table 4D4B (multicore armoured thermoplastic insulated cables with aluminium conductors), the current-carrying capacity for a 25mm cable on a perforated cable tray (Reference Method E) is approximately 80A for a 3- or 4-core cable at 30C ambient temperature and 70C conductor operating temperature.

    Note: The exact value depends on the number of cores (2-core vs 3/4-core) and whether any rating/correction factors (grouping, ambient temperature, thermal insulation) apply. I'd recommend confirming against the actual BS 7671:2018 Table 4D4B for your specific configuration, as the aluminium conductor ratings are lower than the copper equivalents (~102A for copper in the same conditions).

    This is outside my core domain of software engineering -- for critical electrical installations, always verify with the relevant standards documentation or a qualified electrical engineer.