This is what I am doing. 42 kWh battery, 6 kW solar and fully electrified house, 2x EVs. I am able to charge cars at work and so in the depths of winter I am able to run the house by charging during the 3 hour window. There have been just a couple of cold (~2-4 degC) days when the battery was depleted 1-2 hours before the window starts.
As the weather warms and we get more solar exposure we will easily be in excess. We get a very small export rate with a bonus for no energy consumption during peak evening hours which can offset the fixed daily charge.
There are a lot of gotchas that you need to be aware of. 42 kWh is nominal capacity not the actual usable capacity. House load, max grid import and export capacity, max inverter capacity, AC or DC coupled panels, battery charging profile, battery temp are all factors in how much you can charge in the window. For example I have max 15 kW grid draw, with a 10 kW inverter that can charge the battery. I can put in max ~30 kWh into the battery, so I also run other loads in the house to use the other 5 kW capacity. If I go over 5 kW house load the battery charge is clipped to maintain grid import limit.