Technical detail question: if all of those batteries were on connecting allowing feeding back to the grid, would they be able to synchronise the frequency/phase? What's the threshold/requirement for that to happen?


Replies

crote • today at 12:41 PM

It can be done, but it would requires additional equipment. Batteries are traditionally grid-following, so they'll just follow whatever frequency the grid is already running on. The frequency itself is then provided by the rotational inertia of "spinning metal" power plants.

But there's no reason that has to be your frequency source. Any single battery installation on its own is perfectly capable of making up some frequency, which is why home power banks with island-mode AC output are a thing - or even just a traditional UPS. Doing the same with thousands of individual battery installations across the grid? You'll need some way to get everyone to agree exactly on frequency and phase, which in practice is probably going to mean getting them to agree on time to within a few microseconds, which could be done (albeit not very sabotage-proof) using GPS.

➕ show 2 replies
bob1029 • today at 1:34 PM

> What's the threshold/requirement for that to happen?

The RoCoF (rate of change of frequency) must be low enough that the inverters can form the grid without letting out the magical smoke. Having inertia is what slows this rate down.