bob1029 • today at 2:36 PM • 1 reply • view on HN

I'm not sure I agree with the conclusion that this is merely caused by UPS system control logic. That is an extreme amount of coordination across a lot of makes, models and configurations.

The FFT indicates this is a periodic signal, not a once a day or week thing. It's happening continuously all day every day. I don't know of any UPS systems that perform tests with this kind of regularity.

In any case, I refuse to believe an external sync signal is causing this. The more likely explanation is that the active elements are pulling each other to a common mode due to being physically coupled on the same grid. This is like how clocks on the same beam will synchronize.

https://en.wikipedia.org/wiki/Injection_locking


Replies

the8472 • today at 2:47 PM

The external sync here is NTP. Synchronized clocks + timer-scheduled actions → globally synchronized behavior

From the article:

> The origin of these current peaks was independently confirmed by the manufacturer to be periodic self-tests executed by the battery EMS, confirming our interpretation. Similar minute-scale diagnostic routines are also documented for other commercial UPS systems (cf. Supplementary Note 8).

https://www.snaptec.com.au/akkutec-4801-din-user-manual.pdf

> battery circuit testing 1 x per minute for 1 sec

https://adelsystem.com/hubfs/PDF%20DC-UPS/Instruction%20Manu...

> The battery testing is carried out automatically every 60 sec.

➕ show 1 reply