Interesting. The Sequence of Operations we write for the data halls I work on specifically do not shut down the CRACs on smoke alarm for this reason. The International Mechanical Code (IMC) specifically allows this where a air handler over 2000 cfm serves only one space because it's recognized that it will not spread smoke around a building. 2000 cfm is the threshold where you typically have to install smoke detectors, and typically they do shut down on smoke detection.

The CRAC won't feed a fire oxygen as it's just recirculating the same oxygen depleted air.


Replies

bergeyboy • today at 6:48 PM

While CRACs won't recirculate oxygen, they can move air past sprinklers faster than they can handle which can delay operation, typically 5 fps. Although that's only if you are using sprinklers, clean agent is a different matter.