45°C inlets just killed the chiller. Most people haven't noticed yet

103 points • by magoghm • today at 1:48 PM • 31 comments • view on HN

Comments

helsinkiandrew • today at 3:25 PM

Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178

I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan

➕ show 1 reply
iamniels • today at 3:33 PM

This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.

I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.

➕ show 1 reply
__MatrixMan__ • today at 3:18 PM

That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.

➕ show 3 replies
yread • today at 3:05 PM

Datacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling

➕ show 2 replies
ZiiS • today at 3:51 PM

I know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.

ExoticPearTree • today at 3:33 PM

ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).

The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.

Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.

As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.

quickthrowman • today at 3:31 PM

Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.

1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling

Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.

https://mitchellt.com/2018/10/23/why-is-55-so-important.html

The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)

cucumber3732842 • today at 2:59 PM

Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?

There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.

➕ show 2 replies